VSC fault characteristic analysis and diagnosis research of VSC-HVDC
DOI:10.7667/PSPC160015
Key Words:VSC-HVDC  voltage source converter  fault characteristics  fault harmonic transfer law  fault location
Author NameAffiliation
SUN Xiaoyun College of Communication and Information Engineering, Xi’an University of Science and Technology, Xi’an 710054, China 
GAO Xin Northwest Subsection of State Grid Corporation of China, Xi’an 710048, China 
LIU Yanhua State Grid Shandong Electric Power Company, Jinan 250001, China 
Hits: 3312
Download times: 1515
Abstract:In order to recognize voltage source converter (VSC) of VSC-HVDC system fault type and fault location, a simple and rapid method for fault discrimination and location is presented after the analysis of fault characteristics of converter. Based on the system simulation of two-level VSC-HVDC, the DC voltage and DC current fluctuation components mathematical calculation models and two sides AC fault current mathematical calculation models under condition of single-phase disconnection fault are built respectively, the relationship between AC and DC side harmonics is analyzed, and then the VSC fault harmonic transfer law is obtained. According to the VSC fault mathematical models and harmonic transfer law, the harmonic components of DC current, RMS value of AC current and normalized DC component are taken as diagnosis characteristic quantities, then a simple and high-speed fault location method is put forward to identify minor fault locations. The simulation results show that the method presented for fault discrimination and location can accurately identify minor fault type and fault location of VSC in real time, the diagnosis time is up to 35 ms. This work is supported by Scientific Research Program of Shaanxi Education Department (No. 15JK1477).
View Full Text  View/Add Comment  Download reader