Dual model equivalent inductance method for identifying transformer inrush current
CSTR:
Author:
Affiliation:

Clc Number:

Fund Project:

This work is supported by the National Natural Science Foundation of China (No. U1866603) and the Headquarters Technology Project of the State Grid Corporation of China (No. 5100-202340030A-1-1-ZN).

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    Based on the dual equivalent model of a single-phase two-winding transformer and a single-phase three-winding autotransformer, a method for identifying inrush current in single-phase transformers is proposed. This method distinguishes inrush current from internal fault current using the instantaneous equivalent inductance of the dual model. The setting principle of the method is determined by analyzing the air-core inductance and the equivalent model of the faulty transformer. PSCAD simulations and recorded transformer protection data demonstrate that the proposed method can accurately identify inrush current when the transformer core is deeply saturated, and can quickly discriminate between currents during a critical internal fault. Furthermore, the simulation results show that the proposed method is sensitive to minor turn-to-turn faults but is less sensitive to the equivalent impedance of an external source.

    Reference
    Related
    Cited by
Get Citation

Jimin Chai, Yuping Zheng, Shuyan Pan. Dual model equivalent inductance method for identifying transformer inrush current[J]. Protection and Control of Modern Power Systems,2025,V10(04):42-57.[Jimin Chai, Yuping Zheng, Shuyan Pan. Dual model equivalent inductance method for identifying transformer inrush current[J]. Power System Protection and Control,2025,V10(04):42-57]

Copy
Related Videos

Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:
  • Revised:
  • Adopted:
  • Online: July 09,2025
  • Published:
Article QR Code