基于柔性接地装置的不对称配电网接地故障选相选线方法
CSTR:
作者:
作者单位:

(1.智能电网运行与控制湖南省重点实验室(长沙理工大学),湖南 长沙 410114;2.湖南大学,湖南 长沙 410082)

作者简介:

陈柏宇(1996—),男,硕士研究生,研究方向为电力系统保护与控制;E-mail: cboyu@live.com 喻 锟(1989—),男,通信作者,博士,研究方向为电力系统保护与控制;E-mail: 1393009168@qq.com 曾祥君(1972—),男,博士,教授,研究方向为电力系统保护与控制。E-mail: eexjzeng@qq.com

通讯作者:

中图分类号:

基金项目:

国家自然科学基金项目资助(51737002,52037001);湖南省自然科学基金项目资助(2021JJ30729)


A method of phase selection and line selection for grounding faults in an asymmetric distribution network based on a flexible-grounding device
Author:
Affiliation:

(1. Hunan Province Key Laboratory of Smart Grids Operation and Control (Changsha University of Science and Technology), Changsha 410114, China; 2. Hunan University, Changsha 410082, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    配电网高阻接地故障选相和选线一般较为困难。为解决这两个问题,提出了一种基于柔性接地装置的不对称配电网接地故障选相选线方法。首先详细分析各馈线零序电流在中性点零序电压调控前后的变化情况。利用不同调控状态下故障与健全馈线零序等值导纳的离散程度来辨识故障馈线,得出故障馈线辨识函数并构造了选线判据。其次,根据分相调控过程中馈线零序等值导纳与故障前馈线对地导纳差值的相角关系进行故障相判别,得出故障选相函数并构造了选相判据。理论分析和PSCAD/EMTDC仿真实验表明:配电网三相对地导纳不对称情况对所提方法并无影响,低、高阻接地故障时均有较高灵敏度,故障选相与选线结果准确,且选相和选线方法得到有效结合。

    Abstract:

    It is generally difficult to select high-resistance ground fault phases and fault lines in distribution networks. This paper proposes a new method of phase selection and line selection for high-resistance faults in asymmetric distribution networks based on a flexible-grounding device. First, the change characteristic of the zero-sequence current of each feeder before and after zero-sequence voltage regulation is analyzed in detail. It identifies the fault feeders using the dispersion degree of zero-sequence equivalent admittance of the faulted feeder and the healthy feeder in different regulation and control states. Thus the fault line identification function is obtained and a line selection criterion is constructed. Secondly, the fault phase is identified according to the angular relationship between the zero-sequence equivalent admittance of the feeder during the phase separation adjustment process and the ground admittance value of the feeder before the fault. The fault phase selection function is derived and the phase selection criterion is constructed. Theoretical analysis and PSCAD/EMTDC simulation show that the asymmetry of the three-phase ground admittance of the distribution network has no effect on the method proposed. Both low and high resistance ground faults have higher sensitivity in the method, the fault phase selection and line selection results are accurate, and the phase selection and line selection methods are effectively combined. This work is supported by the National Natural Science Foundation of China (No. 51737002 and No. 52037001).

    参考文献
    相似文献
    引证文献
引用本文

陈柏宇,喻 锟,曾祥君,等.基于柔性接地装置的不对称配电网接地故障选相选线方法[J].电力系统保护与控制,2022,50(12):1-11.[CHEN Boyu, YU Kun, ZENG Xiangjun, et al. A method of phase selection and line selection for grounding faults in an asymmetric distribution network based on a flexible-grounding device[J]. Power System Protection and Control,2022,V50(12):1-11]

复制
分享
相关视频

文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2021-08-13
  • 最后修改日期:2021-11-24
  • 录用日期:
  • 在线发布日期: 2022-06-16
  • 出版日期:
文章二维码
关闭
关闭