混合直流输电系统送端交流暂态电压特性研究
CSTR:
作者:
作者单位:

(国网经济技术研究院有限公司,北京 102209)

作者简介:

索之闻(1988—),男,通信作者,博士,工程师,主要研究方向为高压直流输电系统设计及交直流混合电力系统安全稳定分析;E-mail:suozhiwen@126.com
陈启超(1983—),男,博士,工程师,主要研究方向为电力电子变压器、柔性直流输电技术;
李 晖(1981—),男,博士,教授级高工,主要研究方向为智能电网规划。

通讯作者:

中图分类号:

基金项目:

国家电网公司总部科技项目资助(B3440817K003)


Research on sending end AC transient voltage characteristics of hybrid HVDC transmission system
Author:
Affiliation:

(State Grid Economic and Technological Research Institute Co. Ltd., Beijing 102209, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    对于大规模新能源特高压直流外送系统,受端电网故障可能导致送端电网电压剧烈变化,严重威胁送端电网的安全稳定运行,因此送端电网暂态电压是直流输电系统适应性的重要考虑因素。混合直流输电结合了常规直流和柔性直流的优势。针对大规模新能源混合直流外送应用场景,首先介绍了两端混合直流输电系统典型拓扑,建立了相应数学模型,阐述了基本控制结构。然后分析了当受端交流电网发生短路故障,采用不同直流输电拓扑方案时送端电网的交流暂态电压特性。最后在PSCAD/EMTDC搭建了不同混合直流输电系统仿真模型,验证了上述分析的有效性。

    Abstract:

    For large-scale renewable energy UHVDC transmission system, fault happens on the receiving end may cause drastically change on the sending end power grid, which seriously threatens the stability of the sending end power grid. Therefore, voltage characteristic of the sending end is an important consideration for the adaptability of the HVDC transmission system. Hybrid HVDC combines the advantage of LCC-HVDC and VSC-HVDC. In view of the application scenario of large-scale renewable energy transmission through hybrid HVDC, this paper first introduces the typical topologies of two-terminal HVDC transmission system. The corresponding mathematical model is established and the basic control structure is also expounded. Then the AC voltage characteristics of the sending end power grid when short-circuit fault occurs in the receiving end under different hybrid HVDC topologies are analyzed. Finally, the simulation model of different hybrid HVDC topologies is established in the PSCAD/EMTDC simulation platform, and the effectiveness of the above analysis is verified. This work is supported by Science and Technology Project of the Headquarter of State Grid Corporation of China (No. B3440817K003).

    参考文献
    相似文献
    引证文献
引用本文

索之闻,陈启超,李晖,等.混合直流输电系统送端交流暂态电压特性研究[J].电力系统保护与控制,2019,47(17):125-132.[SUO Zhiwen, CHEN Qichao, LI Hui, et al. Research on sending end AC transient voltage characteristics of hybrid HVDC transmission system[J]. Power System Protection and Control,2019,V47(17):125-132]

复制
分享
相关视频

文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2018-09-02
  • 最后修改日期:2018-12-18
  • 录用日期:
  • 在线发布日期: 2019-08-30
  • 出版日期:
文章二维码
关闭
关闭