Reactive power analysis and novel faulty selection method in resonant grounding system
Author:
Affiliation:

(1. State Grid Jiangxi Electric Power Research Institute, Nanchang 330096, China;2. College of Information and Control Engineering, China University of Petroleum (East China), Qingdao 266580, China;3. Shengli Oilfield Shengli Power Machinery Group Co., Ltd., Dongying 257000, China;4. Electric Power Research Institute, Guangxi Power Grid Corporation, Nanning 530023, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    对于谐振接地系统的单相接地故障,由于现场普遍存在电压互感器(PT)和电流互感器(CT)极性反接的现象,当仅仅利用故障的暂态无功功率方向进行选线时极易发生误选。分析了PT、CT极性反接对故障暂态和工频无功功率的影响,提出一种利用故障的工频无功功率对暂态无功功率进行修正再选线的新方法。即:修正后的暂态无功功率为负值的线路为故障线路,如果所有出线修正后的暂态无功功率都是正值则为母线接地。该方法可以忽略PT和CT的极性反接影响,扩大了选线适用范围。仿真和现场的数据证明了该方法的可行性。

    Abstract:

    Because of the incorrect polarity connection of voltage transformer and current transformer in field, faulty feeder selection based on transient reactive power direction leads to wrong easily when there is a single-phase earth fault in resonant grounding system. In this paper, the effect of the incorrect polarity connection of voltage transformer and current transformer on transient reactive power and power-frequency reactive power is analyzed. A novel method using the power-frequency reactive power to correct the transient reactive power for faulty feeder selection is proposed. The faulty feeder is the one which the corrected transient reactive power is negative. If all of the corrected transient reactive powers are positive, it is bus fault. The proposed method is independent of polarity connection of voltage transformer and current transformer, which enlarges the selection scope. The feasibility of the new method is verified by digital simulation and field fault data. This work is supported by National Natural Science Foundation of China (No. 51477184).

    参考文献
    相似文献
    引证文献
引用本文

潘本仁,宋华茂,张秋凤,等.小电流接地故障无功功率分析及选线新方法[J].电力系统保护与控制,2017,45(14):51-56.[PAN Benren, SONG Huamao, ZHANG Qiufeng, et al. Reactive power analysis and novel faulty selection method in resonant grounding system[J]. Power System Protection and Control,2017,V45(14):51-56]