引用本文:张长久,邬小波,谢小英.基于GB/T33593标准的DG低电压穿越输出特性研究[J].电力系统保护与控制,2019,47(24):76-83.
ZHANG Changjiu,WU Xiaobo,XIE Xiaoying.Research on low voltage ride through of DG characteristics based on GB/T33593 standard[J].Power System Protection and Control,2019,47(24):76-83
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4610次   下载 2000 本文二维码信息
码上扫一扫!
分享到: 微信 更多
基于GB/T33593标准的DG低电压穿越输出特性研究
张长久1,邬小波2,谢小英1
(1.国网冀北电力有限公司秦皇岛供电公司,河北 秦皇岛 066000;2.国网冀北电力有限公司,北京 100054)
摘要:
当含分布式电源配电网故障时,需要分布式电源提供电压支撑,要求其具备低电压穿越能力。研究分布式电源的低电压穿越输出特性对配电网故障分析和保护设计具有重要意义。依据《分布式电源并网技术要求》(GB/T 33593-2017)建立了分布式电源低电压穿越控制指令和控制规则,推导出低电压穿越过程中分布式电源故障等效模型,得出分布式电源低电压穿越输出电流表达式,并阐述了含分布式电源配电网故障分析的基本方法。算例仿真结果验证了建模及理论分析的正确性。
关键词:  分布式发电  并网逆变器  低电压穿越  故障分析  故障特性
DOI:10.19783/j.cnki.pspc.190214
分类号:
基金项目:国家自然科学基金项目资助(51777121);国网秦皇岛供电公司2018年群众性创新项目资助(520104170004)
Research on low voltage ride through of DG characteristics based on GB/T33593 standard
ZHANG Changjiu1,WU Xiaobo2,XIE Xiaoying1
(1. Qinhuangdao Power Supply Company, State Grid Jibei Electric Power Co., Ltd., Qinhuangdao 066000, China;2. State Grid Jibei Electric Power Co., Ltd., Beijing 100054, China)
Abstract:
Distributed generation is required to provide voltage support when failure occurred in distribution network connected with distributed generation, and low voltage ride through capability of distributed generation is required. Therefore, investigating the fault output characteristics of distributed generation during low voltage ride through is significant for fault analysis and protection design. According to the technical requirements for grid connection of connected distributed resources (GB/T 33593-2017), the low voltage ride through control instructions and control rules of distributed generation are established in this paper. The fault equivalent model and current description of distributed generation during low voltage ride through are derived. The basic approach of fault calculation for distribution network containing distributed power supplies is discussed. The correctness of the modeling and theoretical analysis is verified by the simulation results of the example. This work is supported by National Natural Science Foundation of China (No. 51777121).
Key words:  distributed generation  grid connected inverter  low voltage ride through  fault analysis  fault characteristic