引用本文:马伟东,孔圣立,刘超,等.基于联合电压判据的高压并联电容器单相接地故障保护方法[J].电力系统保护与控制,2019,47(22):142-147.
MA Weidong,KONG Shengli,LIU Chao,et al.Single-phase earth fault protection method based on combined voltage criterion in high voltage shunt capacitor[J].Power System Protection and Control,2019,47(22):142-147
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4635次   下载 2076 本文二维码信息
码上扫一扫!
分享到: 微信 更多
基于联合电压判据的高压并联电容器单相接地故障保护方法
马伟东,孔圣立,刘 超,宋 闯,刘 尧
(国网河南省电力公司电力科学研究院,河南 郑州 450052)
摘要:
针对目前电容器组单相接地故障保护存在的不足,提出了一种通过比较三相对地电压来进行单相接地故障判别的联合电压判据保护方法。对构造联合电压判据的电压幅值比较法和电压相位比较法进行了理论分析,给出了保护定值的计算方法。通过分析比较两种方法的优劣,推荐采用电压幅值比较法来构造联合电压判据,并通过仿真计算,验证了联合电压判据的可行性。由于只有在三相电压均满足条件时,保护才能动作,故联合电压判据具备较好的防止PT断线造成保护误动的能力。
关键词:  联合电压  电压幅值  电压相位  比较  并联电容器  单相接地
DOI:10.19783/j.cnki.pspc.181608
分类号:
基金项目:国家电网有限公司科技项目资助(52170218000M)
Single-phase earth fault protection method based on combined voltage criterion in high voltage shunt capacitor
MA Weidong,KONG Shengli,LIU Chao,SONG Chuang,LIU Yao
(State Grid Henan Electric Power Research Institute, Zhengzhou 450052, China)
Abstract:
In allusion to the insufficiency of capacitor bank single-phase fault protection at present, this paper puts forward a combined voltage criterion protection method by comparing three-phase ground voltage to distinguish the single-phase earth fault. Aiming at constructing combined voltage criterion, voltage value comparison method and voltage phase comparison method are analyzed theoretically and a protection setting calculation method is given. Through analyzing and comparing the advantage and disadvantage of the two methods, voltage value comparison method is recommended to construct the combined voltage criterion. Furthermore, the feasibility of combined voltage criterion is verified by simulation. Since the protection will act only if all the three phase voltages are satisfied, the combined voltage criterion has a better function to prevent protection misoperation caused by PT breaking. This work is supported by Science and Technology Project of State Grid Corporation of China (No. 52170218000M).
Key words:  combined voltage  voltage value  voltage phase  comparing  shunt capacitor  single-phase earth fault