引用本文:王友怀,张浩,周虎兵,等.计及涌流影响的零序电流保护风险评估[J].电力系统保护与控制,2019,47(10):120-126.
WANG Youhuai,ZHANG Hao,ZHOU Hubing,et al.Risk assessment of zero sequence current protection considering inrush current[J].Power System Protection and Control,2019,47(10):120-126
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4517次   下载 2214 本文二维码信息
码上扫一扫!
分享到: 微信 更多
计及涌流影响的零序电流保护风险评估
王友怀1,张 浩1,周虎兵1,张焕青1,洪 悦1,殷建军2
(1.国网湖北省电力有限公司,湖北 武汉 430077;2.北京四方继保自动化股份有限公司,北京 100085)
摘要:
针对高压内置变压器空投导致零序电流保护误动的问题,从系统层面研究计及涌流影响的零序电流保护风险评估,以完善现有风险评估模型在涌流场景下未涉及盲区的不足。考虑影响涌流产生的多因素并非完全可得,提出了一种计及参量完备性的误动概率计算模型。在参量信息缺失不可得时,利用电网设备状态监测数据库中的数据补充计算,并分配相应的权重得到综合加权误动概率。在此基础上给出了具体风险指标和操作建议。通过具体的算例对所提出的风险评估方法进行展示,评估结果与实际运行中线路和母联动作结果一致。
关键词:  励磁涌流  零序电流保护  风险评估  误动概率模型
DOI:10.7667/PSPC20191016
分类号:
基金项目:国网湖北省电力公司项目资助(26150515003C);国家自然科学基金项目资助(51207113)
Risk assessment of zero sequence current protection considering inrush current
WANG Youhuai1,ZHANG Hao1,ZHOU Hubing1,ZHANG Huanqing1,HONG Yue1,YIN Jianjun2
(1. State Grid Hubei Electric Power Company, Wuhan 430077, China;2. Beijing Sifang Automation Co., Ltd., Beijing 100085, China)
Abstract:
Aiming at the problem of zero sequence current protection caused by high voltage built-in transformer, the risk assessment of zero sequence current protection considering the impact of inrush is studied from the system level in order to improve the shortage of existing risk assessment model in the inrush scene. Considering the multiple factors affecting inrush current is not entirely available, a calculation model of malfunction probability considering the completeness of parameters is proposed. When the missing parameter information is not available, the comprehensive weighted misoperation probability is obtained by using the data in the monitoring database of the power grid equipment state and assigning the corresponding weight. On this basis, specific risk indicators and operational suggestions are given. In this paper, a specific example is given to demonstrate the proposed risk assessment method, and the results are consistent with the actual operation of the line and bus action results. This work is supported by Project of State Grid Hubei Electric Power Company (No. 26150515003C) and National Natural Science Foundation of China (No. 51207113).
Key words:  magnetizing inrush current  zero sequence current protection  risk assessment  misoperation probability model