引用本文:吴书煜,马宏忠,姜宁,等.基于多物理场耦合的高压电抗器温度场仿真与分析[J].电力系统保护与控制,2019,47(4):17-24.
WU Shuyu,MA Hongzhong,JIANG Ning,et al.Simulation and analysis of temperature field of high voltage reactor based on multi physical field coupling[J].Power System Protection and Control,2019,47(4):17-24
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 6649次   下载 2696 本文二维码信息
码上扫一扫!
分享到: 微信 更多
基于多物理场耦合的高压电抗器温度场仿真与分析
吴书煜1,马宏忠1,姜 宁2,田 涛2,陈 轩2,谭风雷2
(1.河海大学能源与电气学院,江苏 南京 211100;2.国网江苏省电力有限公司检修分公司,江苏 南京 211102)
摘要:
为研究干式空心电抗器整体及包封内部各层绕组温度分布特性,根据电磁热流多物理场耦合方法,建立了干式空心电抗器电磁-流体-温度三维温升计算模型。首先,基于场-路耦合的电磁学理论,采用有限元法求取电抗器各层电流,计算各层绕组损耗。然后,基于流体-温度耦合的传热理论,以各层绕组损耗为热源,采用有限体积法求解电抗器温度分布。最后,采用稳态热学分析法验证了结果的准确性。研究结果表明:电抗器温度分布呈现上区域大于下区域、中间包封大于两侧包封的变化趋势,各层绕组温升热点位于电抗器轴向高度约85%到90%。研究结果为电抗器结构优化、温度的在线监测提供了理论依据。
关键词:  干式空心电抗器  损耗计算  多物理场耦合  温度场
DOI:10.7667/PSPC180220
分类号:
基金项目:国家自然科学基金项目资助(51577050);国网江苏省电力有限公司2018年重点科技项目资助(J2018014)
Simulation and analysis of temperature field of high voltage reactor based on multi physical field coupling
WU Shuyu1,MA Hongzhong1,JIANG Ning2,TIAN Tao2,CHEN Xuan2,TAN Fenglei2
(1. College of Energy and Electrical Engineering, Hohai University, Nanjing 211100, China;2. Maintenance Branch Company, State Grid Jiangsu Electric Power Co., Ltd., Nanjing 211102, China)
Abstract:
In order to study the temperature distribution characteristics of the whole and inner layer winding of dry-type air-core reactor, a three dimensional temperature rise calculation model of electromagnetic-fluid-temperature of dry-type air-core reactor is established based on the multi physical field coupling method of electromagnetic heat flux. First of all, based on the electromagnetism theory of field-circuit coupling, current of each layer of the reactor was calculated by finite element method and the winding loss of each layer is calculated. Then, based on the heat transfer theory of fluid-temperature coupling, taking the winding loss of each layer as the heat source, the finite volume method is used to solve the reactor temperature distribution. Finally, the accuracy of the results is verified by the steady-state thermal analysis method. The results show that the temperature distribution of the reactor shows the trend that the upper region is larger than the lower one and the middle enclosure is larger than the two sides. The hot spot temperature rise of each layer is about 85%~90% of the reactor axial height. The research results provide a theoretical basis for the optimization of the reactor structure and the on-line monitoring of the temperature. This work is supported by National Natural Science Foundation of China (No. 51577050) and Key Science and Technology Projects of State Grid Jiangsu Electric Power Co., Ltd. in 2018 (No. J2018014).
Key words:  dry-type air-core reactor  loss calculation  multi physical field coupling  temperature field
  • 1
X关闭
  • 1
X关闭