引用本文:贺敏,徐光福,伊洋,等.含高渗透率DG的配电网实用化保护方案[J].电力系统保护与控制,2017,45(17):136-143.
HE Min,XU Guangfu,YI Yang,et al.A practical protection scheme for distribution network with high penetration of DG[J].Power System Protection and Control,2017,45(17):136-143
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 5674次   下载 2604 本文二维码信息
码上扫一扫!
分享到: 微信 更多
含高渗透率DG的配电网实用化保护方案
贺敏1,徐光福2,伊 洋3,余群兵2,朱皓斌2
(1.国网电力科学研究院,江苏 南京 211106;2.南京南瑞继保电气有限公司,江苏 南京 211102; 3.广州供电局有限公司,广东 广州 510620)
摘要:
分析了高渗透率DG接入配网对传统三段式过流保护的影响。为了解决三段式过流保护可能存在的误动、拒动问题,提出了一种含高渗透率DG的配电网实用化保护方案并给出了保护配置及整定原则。该保护方案基于重合闸前加速保护、防孤岛保护和合于故障保护之间的时序配合,不依赖于通信且无需装设大量PT,保护定值整定按照常规配网无DG接入条件下整定,不受DG接入的数量、容量和位置影响。RTDS仿真结果表明,所提出的保护方案实用、有效,能够在含高渗透率DG接入环境下准确隔离配网故障。
关键词:  高渗透率DG  前加速保护  合于故障保护  防孤岛保护  时序配合
DOI:10.7667/PSPC161314
分类号:
基金项目:广州供电局有限公司科技项目(K-GZM2014-144)
A practical protection scheme for distribution network with high penetration of DG
HE Min1,XU Guangfu2,YI Yang3,YU Qunbing2,ZHU Haobin2
(1. State Grid Electric Power Research Institute, Nanjing 211106, China;2. NR Electric Co., Ltd., Nanjing 211102, China;3. Guangzhou Power Supply Bureau Co., Ltd., Guangzhou 510620, China)
Abstract:
The influence of high permeability DG access to distribution network on the traditional three stage over-current protection is analyzed. A practical protection scheme for distribution network with high penetration of DG is proposed to solve the problem of the possible mal-operation of the three stage over-current protection, and also the protection configuration and setting principle are proposed. The protection scheme is based on sequential coordination between instant accelerate protection, anti-islanding protection and switch onto fault protection, having no dependence on communication and a large number of PTs, and the settings are set according to the conventional distribution network without DG access, which are not affected by the number, capacity and position of DG access. RTDS simulation result shows that the protection scheme is practical and effective and it can isolate the distribution network fault accurately within high permeability DG..
Key words:  high penetration of DG  instant accelerated protection  switch onto fault protection  anti-island protection  sequential coordination