一种同名相转换性故障变压器差动保护防拒动的研究
陈继瑞1,张营伟2,邓茂军1,姚东晓1
(1.许继电气公司技术中心,河南 许昌 461000;2.许继风电科技有限公司,河南 许昌 461000)
摘要:
为解决变压器差动保护在发生区外故障CT饱和转区内同名相故障CT饱和导致的差动保护拒动问题,提出一种差流点差饱和开放识别方案。若为单电源CT饱和时饱和段差流采样点将会很小或出现间断。若为多电源单CT饱和时差流趋于正常波形。利用差流采样点的比率制动关系及制动电流间断角的特性,通过识别一周波内满足比率制动特性与间断点的总采样点数,来判断是否区内故障。仿真结果表明,该方法适用于变压器差动保护同名相转换性故障识别。
关键词:  变压器  CT饱和  同名相  间断角  转换性故障  区内饱和
DOI:10.7667/PSPC151312
分类号:
基金项目:
Research of a transformer differential protection against refusing action about the same phase transformation faults
CHEN Jirui1,ZHANG Yingwei2,DENG Maojun1,YAO Dongxiao1
(1. Technology Center, XJ Electric Co., Ltd., Xuchang 461000, China;
;2. XJ Wind Power Technology Co., Ltd., Xuchang 461000, China)
Abstract:
To solve the problem of transformer differential protection refusing action, when outside fault CT saturation transfering the same phase inside fault with CT saturation, this paper puts forward a scheme based on differential current sampling points differentia saturated open. For a single power supplying when differential current sampling points of CT saturation periods will be small or presenting interruptive angles; if multiple power supplying and single CT saturation, differential currents return to normal waveforms. It uses ratio braking relations of differential current sampling point and characteristics of the braking current interruptive angle, by identifying total sampling points of meeting ratio braking characteristics and interruptive points within a cyclic wave, to judge whether the fault in the area. The simulation results show that this method is suitable for the identification of the same phase fault about transformer differential protection.
Key words:  transformer  CT saturation  same phase  interruptive angle  transform fault  the area of saturation