引用本文:白加林,高昌培,王宇恩,等.基于频数分布的防止变压器差动保护误动的新方法[J].电力系统保护与控制,2016,44(8):14-21.
BAI Jialin,GAO Changpei,WANG Yuen,et al.A new algorithm based on frequency distribution for avoiding the mal-operation of transformer differential protection[J].Power System Protection and Control,2016,44(8):14-21
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 6386次   下载 3029 本文二维码信息
码上扫一扫!
分享到: 微信 更多
基于频数分布的防止变压器差动保护误动的新方法
白加林1, 高昌培1, 王宇恩1, 赵武智1, 牛静1, 赵建新2, 黄婷3, 郑涛3
1.贵州电网公司电力调度控制中心,贵州 贵阳 550002;2.北京四方继保自动化股份有限公司技术支持部,北京 100085;3.华北电力大学电气与电子工程学院, 北京 102206
摘要:
为有效防止变压器区外故障因CT饱和引起的差动保护误动,提出了一种基于频数分布的检测CT饱和的新方法。该方法截取从故障发生到差流达到第一个极值之间的部分差流波形并经适当变换,利用频数分布直方图进行电流波形处理。根据频数分布特征,能够实现CT严重饱和、一般饱和、轻度饱和情况下变压器区内外故障的准确检测。该方法只需定位故障发生时刻,而不需定位差流出现时刻,算法简单,快速可靠。经大量仿真实验验证了新方法的可靠性和准确性。
关键词:  变压器保护  差动保护  波形变换  CT饱和检测  频数分布
DOI:10.7667/PSPC151064
分类号:
基金项目:
A new algorithm based on frequency distribution for avoiding the mal-operation of transformer differential protection
BAI Jialin1, GAO Changpei1, WANG Yuen1, ZHAO Wuzhi1, NIU Jing1, ZHAO Jianxin2, HUANG Ting3, ZHENG Tao3
1.Guizhou Power Dispatching and Control Center, Guiyang 550002, China;2.The Beijing Sifang Automation Co., Ltd., Beijing 100085, China;3.School of Electrical and Electronic Engineering,North China Electric Power University, Beijing 102206, China
Abstract:
To avoid the mal-operation of transformer differential protection when out-zone fault occurs under current transformer (CT) saturation, a new algorithm based on frequency distribution is proposed. A new current waveform is obtained by a symmetric transformation of initial part of differential current after fault occurred, and then its characteristic is extracted by frequency distribution histogram. In the case of CT’s serious saturation, medium saturation, mild saturation, the out-zone fault and the inner-zone fault can be clearly detected by the proposed algorithm. This algorithm only needs detecting the time of fault occurring, while the time of differential current increasing is no more needed, the proposed algorithm is very fast and reliable. Simulation show satisfactory results and validate its flexibility and reliability.
Key words:  transformer protection  differential protection  waveform transformation  CT’s saturation detection  frequency distribution
  • 1
X关闭
  • 1
X关闭