引用本文:王秀莲,胡广,毕大强.光伏低电压穿越期间无功补偿对差动保护 灵敏度的影响分析[J].电力系统保护与控制,2016,44(4):51-56.
WANG Xiulian,HU Guang,BI Daqiang.Impact analysis of reactive power compensation on sensitivity of differential protection during the low voltage ride-through of photovoltaic systems[J].Power System Protection and Control,2016,44(4):51-56
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4645次   下载 2687 本文二维码信息
码上扫一扫!
分享到: 微信 更多
光伏低电压穿越期间无功补偿对差动保护 灵敏度的影响分析
王秀莲1, 胡广1, 毕大强2
1.沈阳理工大学,辽宁 沈阳 110168;2.清华大学电机系电力系统国家重点实验室,北京100084
摘要:
研究了具备低电压穿越(Low Voltage Ride-Through,LVRT)能力的光伏并网发电系统,送出线部分发生三相短路故障时,LVRT控制过程中发出的无功电流对传统比率制动式和新型标积制动式差动保护灵敏度的影响。理论分析表明故障期间无功补偿会导致两种差动保护的灵敏度下降,并通过Simulink搭建光伏并网发电系统仿真模型验证了这一结论。在此基础上,进一步对比得出发生金属性短路故障时,标积制动式差动保护的灵敏度受无功补偿影响较小,作为光伏电站送出线部分的保护效果更佳。最后通过差动特性曲线的整定方式,对如何提升差动保护灵敏度的问题提出改进建议。
关键词:  LVRT  无功补偿  比率制动  标积制动  灵敏度
DOI:10.7667/PSPC150696
分类号:
基金项目:
Impact analysis of reactive power compensation on sensitivity of differential protection during the low voltage ride-through of photovoltaic systems
WANG Xiulian1, HU Guang1, BI Daqiang2
1.Shenyang Ligong University, Shenyang 110168, China;2.State Key Lab of Power Systems, Dept of Electrical Engineering, Tsinghua University, Beijing 100084, China
Abstract:
The influence of reactive power compensation on sensitivity of differential protection of ratio-restraining characteristic and product-restraining characteristic is studied, when the output line of grid-connected photovoltaic (PV) systems with low voltage ride-through capability occurs three-phase short-circuit failures. It is found that the use of LVRT results in the decline of two kinds of sensitivity of the differential protection. The model of grid-connected photovoltaic (PV) system is set up, and verified by Simulink simulation. And further conclusion shows that the impact of differential protection of product-restraining characteristic on sensitivity is smaller, when the reactive power compensation is injected, and is better for the protection of output lines of photovoltaic power station, when the short-circuit fault occurs. Finally, this paper presents recommendations about how to improve the sensitivity of the differential protection by the tuning mode of differential characteristic curve.
Key words:  LVRT  reactive power compensation  ratio-restraint  product-restraint  sensitivity