引用本文:徐岩,刘泽锴,应璐曼.混合MIDC馈入下的工频变化量阻抗方向保护 动作特性分析[J].电力系统保护与控制,2015,43(5):14-20.
XU Yan,LIU Zekai,YIN Luman.Performance of impedance directional protection based on variation of power-frequency components in hybrid multi-infeed HVDC system[J].Power System Protection and Control,2015,43(5):14-20
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 5164次   下载 2673 本文二维码信息
码上扫一扫!
分享到: 微信 更多
混合MIDC馈入下的工频变化量阻抗方向保护 动作特性分析
徐岩, 刘泽锴, 应璐曼
新能源电力系统国家重点实验室(华北电力大学),河北 保定 071003
摘要:
交流电网故障引发线路换相换流器高压直流(Line Commutated Converter High Voltage Direct Current, LCC-HVDC)换相失败,改变了原有交流电网工频变化量方向保护动作特性。针对这一问题,建立了由电压源换流器高压直流(Voltage Source Converter HVDC, VSC-HVDC)系统与LCC-HVDC系统组成的混合多馈入直流(bybrid multi-infeed HVDC,HMIDC)输电系统模型,并与馈入同一交流电网的单条LCC-HV
关键词:  线路换相换流器高压直流  电压源换流器高压直流  混合多馈入直流  工频变化量  方向纵联保护  换相失败
DOI:10.7667/j.issn.1674-3415.2015.05.003
分类号:
基金项目:
Performance of impedance directional protection based on variation of power-frequency components in hybrid multi-infeed HVDC system
XU Yan, LIU Zekai, YIN Luman
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources (North China Electric Power University), Baoding 071003, China
Abstract:
The LCC-HVDC commutation failure caused by AC power network fault affects the operation of directional protection based on power-frequency component variation for AC transmission lines. A hybrid multi-infeed HVDC system model consisted of a VSC-HVDC system and a LCC-HVDC system is set up, compared with a AC/DC system of a single LCC-HVDC system fed into the same AC grid. Combined with the characteristic of the analysis of power-frequency component variation based on the principle of directional protection, the performance of LCC-HVDC equivalent impedance of power-frequency component variation is quantitatively analyzed under the same commutation failure in LCC-HVDC system of this two different transmission structures. The simulations of two different structures for the same commutation failure of HVDC in identical fault simulated by PSCAD/EMTDC testify the accuracy and validity of the theory analysis. It indicates that the hybrid multi-infeed HVDC system can improve the impact of directional protection based on power-frequency component variation caused by the LCC-HVDC commutation failure and provides the theoretical basis for the power network planning.
Key words:  line commutated converter high voltage direct current  voltage source converter HVDC  hybrid multi-infeed HVDC  power-frequency component variation  directional pilot protection  commutation failure
  • 1
X关闭
  • 1
X关闭