引用本文:吕颖,孙树明,汪宁渤,等.大型风电基地连锁故障在线预警系统研究与开发[J].电力系统保护与控制,2014,42(11):142-147.
Lü Ying,SUN Shu-ming,WANG Ning-bo,et al.Study and development of on-line cascading fault early-warning system for large-scale wind power base[J].Power System Protection and Control,2014,42(11):142-147
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4626次   下载 2896 本文二维码信息
码上扫一扫!
分享到: 微信 更多
大型风电基地连锁故障在线预警系统研究与开发
吕颖1, 孙树明1, 汪宁渤2, 訾鹏1, 陈得治1, 周强2, 高凯3, 何晓阳3, 张艳军3
1.中国电力科学研究院,北京 100192;2.甘肃省电力公司风电技术中心,甘肃 兰州 730050;3.国网辽宁电力有限公司,辽宁 沈阳 110006
摘要:
针对大规模风电连锁脱网事故频发,研究并开发了大型风电基地连锁故障在线预警系统。首先分析风电连锁故障的事故特征,确定建立风电连锁故障在线预警系统的关键环节,完善风机模型、建立风机保护模型和无功补偿模型。然后基于在线动态安全评估技术,提出了适合于大型风电基地的连锁故障在线安全预警的方案和基本结构,包括在线数据整合与预想故障集,风电场连锁脱网事故搜索方法,连锁故障严重性评估方法和连锁故障在线预警并行计算方案。研发的系统在电网中进行了实际应用,验证了所提方法的合理性和有效性。
关键词:  风电基地  连锁故障  在线预警
DOI:10.7667/j.issn.1674-3415.2014.11.023
分类号:
基金项目:国家电网公司重大科技项目
Study and development of on-line cascading fault early-warning system for large-scale wind power base
Lü Ying1, SUN Shu-ming1, WANG Ning-bo2, ZI Peng1,1, CHEN De-zhi1, ZHOU Qiang2, GAO Kai3, HE Xiao-yang3, ZHANG Yan-jun3
1.China Electric Power Research Institute, Beijing 100192, China;2.Wind Power Center of Gansu Electric Power Corporation, Lanzhou 730050, China;3.Liaoning Electric Power Company Limited, Shenyang 110006, China
Abstract:
With consideration of large-scale cascading trip-off fault of wind generating, an on-line cascading fault early-warning system for large-scale wind power base is developed. Through the research of fault characteristics for wind generating cascading trip-off, the key links for building up cascading fault on-line early-warning system for wind power base are determined, including improving wind generator model and modeling wind generating protection and reactive compensation device. Based on on-line dynamic security analysis system, the scheme and basic structure of cascading fault on-line early-warning system for wind power base are proposed, including on-line data integration and contingency set, searching strategy for cascading trip-off fault, severity evaluation method for cascading fault, and parallel computing method. The system has been put into practice, which proves the rationality and effectiveness of the proposed method.
Key words:  wind power base  cascading fault  on-line early-warning