引用本文:金恩淑,李晓娜,宋晓刚,等.自适应变压器励磁涌流判据研究[J].电力系统保护与控制,2013,41(20):41-46.
JIN En-shu,LI Xiao-na,SONG Xiao-gang,et al.Study on adaptive criterion of transformer magnetizing inrush current[J].Power System Protection and Control,2013,41(20):41-46
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4698次   下载 200 本文二维码信息
码上扫一扫!
分享到: 微信 更多
自适应变压器励磁涌流判据研究
金恩淑1, 李晓娜1, 宋晓刚1, 刘聪1, 苏东波1
东北电力大学电气工程学院,吉林 吉林 132012
摘要:
基于差流谐波正序分量的变压器励磁涌流判据能够有效识别励磁涌流和内部故障。为了进一步提高差动保护的励磁涌流闭锁可靠性和内部故障动作快速性,分析了变压器端电压及其基波正序分量突变量在励磁涌流和内部故障时的不同特征,由此确定了自适应控制因子Q,并将Q加入到差流谐波正序分量的励磁涌流判据中,进而提出了一种自适应变压器励磁涌流新判据。大量EMTP仿真及动模实验表明:新判据能够在励磁涌流时自动降低涌流制动定值,提高涌流的闭锁可靠性;在内部故障时自动升高涌流制动定值,提高区内故障时保护的动作速度。
关键词:  变压器  差动保护  励磁涌流  自适应保护
DOI:10.7667/j.issn.1674-3415.2013.20.007
分类号:
基金项目:
Study on adaptive criterion of transformer magnetizing inrush current
JIN En-shu,LI Xiao-na,SONG Xiao-gang,et al
Abstract:
The criterion of transformer magnetizing inrush current based on positive sequence component of differential current harmonics can identify inrush and internal fault effectively. In order to further improve the blocking reliability in magnetizing inrush current cases and operation speed in internal fault cases of differential protection, terminal voltage and its mutation in positive sequence component of fundamental harmonic are analyzed respectively in magnetizing inrush cases and internal fault cases. According to their different characteristics, an adaptive control factor Q is determined, which is added to the magnetizing current criterion based on positive sequence of differential current harmonics, then a new adaptive criterion of transformer magnetizing inrush current is proposed. A large number of EMTP simulations and dynamic simulation experiments show that the new criterion can automatically decrease the threshold setting of restraint in inrush cases, so the reliability of inrush blocking is improved, and it can also automatically increase the threshold setting of restraint in internal fault cases, so the operation speed during internal fault conditions is accelerated.
Key words:  transformer  differential protection  magnetizing inrush current  adaptive protection
  • 1
X关闭
  • 1
X关闭
引用本文:
【打印本页】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览次   下载  
分享到: 微信 更多
摘要:
关键词:  
DOI:
分类号:
基金项目:
Abstract:
Key words:  
  • 1
X关闭
  • 1
X关闭